One, continuous power ( COP )The agreed operation carried out under the conditions and in accordance with the manufacturer's maintenance, generator with constant load sustained running and running hours a year without restriction for maximum power.  
 

Second, the basic rate ( PRP )The agreed operation carried out under the conditions and in accordance with the manufacturer's maintenance, generator with variable load runs continuously and the runtime does not limit the number of maximum power. 24h running within the operating cycle of the average power output (Ppp) should be no more than PRP 70%, except with RIC Engine manufacturers agree otherwise. To allow average power output of Ppp than the requirement of high value applications, you should use the power of COP.  
 

Third, the limited time running power ( LTP )The agreed operation carried out under the conditions and in accordance with the manufacturer's maintenance, generator running time per year up to 500h maximum power. 100% limited time running power, run annually for a maximum time of 500h.   
 

Four, emergency stand-by power ( ESP )In the agreed provisions under the operating conditions and the manufacturer's maintenance, once the mains interruption or under the experimental conditions, generator with variable load operation and the running time up to 200h maximum power. 24h permissible average power output during the running cycle should not be more than 70%ESP, unless otherwise agreed with the manufacturer. 